Description
8106-TI-RT
• 4 RTD or resistance*
source inputs
• Function defined by configuration
• 2-, 3- or 4-wire RTD types
accommodated
MODULE SPECIFICATION
See also System Specification
INPUTS
Number of channels
• 4
RTD input (2,3, or 4 wire)
• Pt100 to BS1904/DIN43760/IEC 75
• Ni120; jPt100 to JIS C1604: 1989
Input resistance range (span)
• 0 to 500 Ω
RTD excitation current
• 200 μA (nom.)
Resolution
• 15 bits plus sign bit
Common mode rejection
• > 80 dB @ 50/60 Hz
Series mode rejection
• > 40 dB @ 50/60 Hz
Isolation
• Any channel to Railbus – 250 V ac rms
Open circuit bleed current
• 0.5 μA (nom.)
CONFIGURABLE PARAMETERS
Sensor type
• User selection
Input deadzone
• User defined value
Selectable input filtering
• Off / 2-reading average / running average
Drive on open circuit fault
• Disabled / upscale
Alarms
• High and low
Channel status
• Active / Inactive
Offset (2-wire RTD mode)
• User defined value
RESPONSE TIME
Signal change to availability on Railbus
• 180 ms (min.)
• 840 ms (max.)
O/C sensor detection
• ≤ 10 s
SAFETY
FM non-incendive field wiring parameters
(each channel)
• Voc = 10.5 V; Isc = 3.6 mA; Ca
= 14.9 μF; La
= 1000 mH
POWER SUPPLIES
Railbus (12V) current
• 1150 mA (typ.)
• 200 mA (max.)
Bussed Field Power
• Not required
MECHANICAL
Module Key Code
• C3
Module width
• 42 mm
Weight
• 200 g
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!