3500/60 BENTLY NEVADA modular

3500/60 BENTLY NEVADA modular

Accepts from 1 to 6 RTD or TC
transducer signals.
Input
Impedance
10 M for each lead input.
Power
Consumption
3500/60: Nominal consumption of
7 watts.
3500/61: Nominal consumption of
9 watts.
Tranducers
TCs
Type E: -100 C to +1000 C,
(-148 F to +1832 F).
Note: When using any of the
isolated thermocouple I/O modules
(-03 or -04 I/O ordering option)
with Type E thermocouples, the
available full-scale range will be
reduced if the 3500 system is
operated in an ambient
temperature above +35C. The
reduced range will be -60C to
+1000C (-76F to +1832F). Rack
configuration software will allow
the user to configure a channel
down to -100C but the system will
not function properly in this
scenario and therefore should not
be configured to operate with
these settings.
Type J: -18 C to +760 C,
(+0 F to +1400 F).
Type K: -18 C to +1370 C,
(+0 F to +2498 F)

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

Description
The 3500/60 & 61 modules provide six channels of
temperature monitoring and accept both Resistance
Temperature Detector (RTD) and Thermocouple (TC)
temperature inputs. The modules condition these inputs
and compare them against user-programmable alarm
setpoints. The 3500/60 and 3500/61 provide identical
functionality except that the 3500/61 provides recorder
outputs for each of its six channels while the 3500/60 does
not.
The user programs the modules to perform either RTD or
TC temperature measurements using the 3500 Rack
Configuration Software. Different I/O modules are
available in RTD/TC non-isolated or TC isolated versions.
The user can configure the RTD/TC non-isolated version to
accept either TC or RTD, or a mixture of TC and RTD inputs.
The TC isolated version provides 250 Vdc of channel-tochannel isolation to protect against external interference.
When used in a Triple Modular Redundant (TMR)
configuration, temperature monitors must be installed
adjacent to each other in groups of three. When used in
this configuration, the system employs two types of voting
to ensure accurate operation and to avoid single-point
failures

BENTLY NEVADA  3500/60

BENTLY NEVADA 3500/60

f6f255eab6fd5a07c60d 3500/60 BENTLY NEVADA modular

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!