If the Trusted System is Modbus Slave, then it has no control over the messages received

from the Master. If the Trusted System is delaying more than expected between messages,

it is possible that insufficient time is allowed for communications processing between the CI

and the Processor. It is possible to allocate some time to background tasks like this by

specifying a sleep period between scans in the system configuration.

This is especially a problem with systems that have no native I/O, e.g. bridged systems, and

therefore do not have communications processing time allocated.

In the system configuration processor parameters shown below, set the sleep period to

approximately 32 ms longer than the ‘current’ scan time seen in the Toolset debugger

window. This will provide some time on most scans for communications tasks, and will even

out the scan time. It will also lengthen the scan time, so ensure that process safety times are

not compromised and the maximum scan time and I/O module watchdog times are adjusted

proportionately to the change in average scan time.

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

ICS TRIPLEX T8151B
The Trusted® Communications Interface (CI) is an intelligent module that provides a range of
communication services for the Trusted Controller, minimising communication loading of the Triple
Modular Redundant (TMR) Processor.
A user-configurable module, the CI can support multiple communication media.
Up to four Communications Interfaces (CIs) can be supported by a Trusted System.
Features:
• Trusted Operating System.
• Dual Ethernet and four serial ports.
• Support for a wide range of communication protocols.
• Secure, dependable communications via high performance communications links.
• Modbus Slave.
• Optional Modbus Master (with T812X Trusted Processor Interface Adapter).
• Optional Sequence Of Events (SOE) Over Modbus.
• Front Panel serial diagnostic port, fault and status indicators
This port operates at 19200 baud on RS232. A command line diagnostic protocol is available
via this port, accessed using a TC-304-01 Maintenance Cable and a terminal program. This
protocol is not affected by the Processor Front Panel keyswitch.
3.1.2. Rear Serial Ports
These ports may be configured between 1200 and 115200 baud. All four ports support
RS485, port 1 supports RS232 with full handshaking and port 2 supports RS232 without
handshaking. These ports can be allocated as a Modbus Remote Terminal Unit (RTU) Slave
or Master (Modbus Master requires a T8122 or T8123 Processor Interface Adapter).
3.1.3. Ethernet Ports
These ports can each support multiple protocols simultaneously.
• Modbus RTU Slave, packaged as a serial stream on Ethernet. This is appropriate for
conversion to serial Modbus at terminal servers or for the Trusted OPC servers and
SOE/Process Historian collector. Up to ten connections can be made to Ethernet
slaves, and the port only needs to be allocated once. Port 2000 is used by default.
The slave can either actively make a connection (appropriate for some terminal
servers) or wait for a connection.
• Open Modbus Transport Control Protocol (TCP), an Ethernet Modbus protocol
designed by Modicon. This will automatically operate if port 502 is selected. Only
Modbus Slave is available on this protocol.
• Modbus RTU Master, packaged as a serial stream on Ethernet. This is enabled by
fitting a T8122 or T8123 Processor Interface Adapter. The Master only makes one
connection, so it may connect to one Ethernet based slave or to one chain of slaves
on a serial link via a terminal server. Each CI can control up to 16 Modbus Masters,
communicating with up to 64 Slaves total, with up to 400 messages total. Each
Master, Slave and message can be individually controlled and monitored, including
statistical data. A Modbus Master can also broadcast messages to some or all Slaves
simultaneously.
• SOE over Modbus protocol. A section of the Modbus address map is used as an
event buffer for SOE events (not Process Historian). This requires programming in
the remote end to poll the data block (with a Modbus Master) and interpret the

c2ca238ad01cd1a2ed0a 1 ICS TRIPLEX T8151B

eaf8abdccd491db4a706 1 scaled ICS TRIPLEX T8151B

d200ac0531f7466be492 1 scaled ICS TRIPLEX T8151B

92fa9914185de84e8083 1 scaled ICS TRIPLEX T8151B

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!