HIMA X-DI1601 985210222

¥8,888.00

HIMA X-DI1601 985210222
Designation
Description
F1DI 16 01
Remote VO (16 digital inputs),
Operating temperature: ..+60 C,
for ELOP Factory programming tool
F1 DI 16 011
Remote VO (16 digital inputs),
(-20 C) .
Operating temperature: -0…+60 C,
for ELOP Il Factory programming tool
F1 DI 1601
Remote 10 (16 digital inputs),
SILworX
Operating temperature: …+.60 C,
for SIL worX programming tool
F1 DI 16 011
Remote 10 (16 digital inputs),
SILworX
Operating temperature: -0…+.0 C,
(-20 C)
for SIL worX programming tool
F1DI 16 014
Remote 10 (16 digital inputs),
SILworX
Operating temperature: 25… +70 C (temperature class T1),
Vibration and shock tested according to EN 50125-3 and EN 50155,
class 1B according to IEC 61373, ,
for SILworX programming tool

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

Product Description
The satety-related F1 DI 16 01 remote I0 is a compact system in a metal housing with
16 digital inputs and 4 pulsed outputs.
The remote VO is avallable in varlous model variants for SILworX and ELOP II Factory, see
Table 4.
Remote /Os are connected to individual HIMax or HIMatrix controllers via safeethernet. They
are used to extend the 1/0 level, but are not able to run any user program by themselves.
The remote Vo is suitable tor mounting in Ex- zone 2, see Chapter 4.1.4.
The device is TOV-certilied for salety-related applications up to SIL 3 (EC 61508, IEC 61511
and IEC 62061), Cat. 4 and PL e (EN ISO 13849-1) and SIL 4 (EN 50126, EN 50128 and
EN 50129).
Further safety standards, application standards and test standards are specified in the
certifcates available on the HIMA website.
Safety Function
The remote VO is equpped with safety-elated inputs. The input values on the inputs are safely
transmitted to the connected controller via safeethernet.
Safety -Related Digital Inputs
The remote VO is equipped with 16 digital inputs. The slate (HIGH, LOW) of each input is
signaled by an individual LED.
Mechanical contacts without own power supply or signal power source can be connected to the
inputs. Potential-free mechanical contacts without own power supply are fed via an intemnal
short-circuit-proof 24 V power source (LS+). Each 24 V power source supplies a group of
4 mechanical contacts. Figure 1 shows how the connection is performed.
With signal voltage sources, the corresponding ground must be connected to the input (L-), see
Figure 1.

4d38d9c118bbd4e5693a 2 HIMA X-DI1601 985210222

08f94a4ec1848818e8e6 2 HIMA X-DI1601 985210222

331bc7be2e26042b07a6 2 HIMA X-DI1601 985210222
Reaction in the Event of a Fault
If the device detects a fault on a digital input, the user program processes a low level in
accordance with the de-energized to trip principle.
The device activates the FAULT LED.
In addition to the channel signal value, the user program must also consider the corresponding
error code.
The error code alows the user to configure additional fault reactions In the user program.
Line Control
Line control is used to detect short circuits or open-circuits and can be configured for the remote
I/O, e.g. on EMERGENCY STOP inputs complying with Cat. 4 and PL e in accordance with
EN IsO 13849-1.
To this end, connect the pulsed outputs TO 1..O 2 of the system to the digital inputs (DI) of
the same system as follows:

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!