408368 IAM MODULE
IDNet or MAPNET II addressable communications
supply both data and power over a single wire pair
to provide**:
Supervised Class B monitoring of normally open, dry
contacts
Total wiring distance from IAM to supervision
resistor(s) of up to 500 ft (152 m)
Monitored connection is compatible with Simplex®
2081-9044 Overvoltage Protectors for outdoor wiring or
electrically noisy applications
For use in indoor locations up to 158° F (70° C) such as
attic spaces or similar applications
For use with following Simplex control panels:
Model Series 4007ES, 4008, 4010, 4010ES, and 4100ES
fire alarm control panels for IDNet communications
Model Series 4100/4100U/4100ES, 4120, 4020, and
2120 Communicating Device Transponders (CDTs)
equipped with MAPNET II communications
Model 4090-9001:
Enclosed design minimizes dust infiltration
Mounts in standard single gang electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers are available to allow LED to be
viewed after installation (requires mounting bracket,
ordered separately)
Model 4090-9051:
Encapsulated design for extended exposure to high
humidity (LED is not present on this model)
Color coded 18 AWG leads for wiring
IDNet communications provides current limited
monitoring:
Provides monitoring of tamper switch (supervisory)
and waterflow switch (alarm) on same circuit using
one point
Available with IDNet communications only
Multiple operation modes are available and are
selectable at the control panel:
Contact closure status can be tracked
Momentary contact closure conditions can be selected at
the panel to be latched or tracked (not available with the
2120 CDT)
UL listed to Standard 864
IGNALING DEVICE
SUE NO.
4090-9051 Supervised IAM
(shown approximately 3/4 size)
Description
Individual addressable modules (IAMs) receive
both power and communications from a two-wire
MAPNET II or IDNet circuit. They provide location
specific addressability to a single initiating device (such
as single station smoke detector alarm contacts or heat
detector contacts) or multiple devices at the same location
by monitoring normally open dry contacts and the wiring
to an end-of-line resistor.
Model 4090-9001 is packaged in a thermoplastic
housing and provides screw terminal connections and a
status indicating LED.
Model 4090-9051 is an encapsulated package with wire
leads. It does not provide a status indicating LED.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!