Description
Feature Specification
1 Points 32, commoned
2 Nominal input voltage 24 VDC
3 Operational voltage range 15–30 VDC
4 Absolute maximum input voltage 33 VDC
5 Absolute maximum reverse input voltage – 0.6 VDC
6 Input delay <10 ms, On to Off or Off to On TC = 6.4 ms, –3dB @ 25Hz
7 Input impedance >30 k:, without baseplate |3 k:, with baseplate
8 Input power 0.2 W/pt, @ 24 VDC 0.5 W/pt, @ 33 VDC
9 Input threshold 0–5 VDC = Off region 6–14 VDC = transition region 15–30 VDC = On region
10 Diagnostic (loss of view) Force-to-value diagnostic (FVD), <2 ms/test
11 Maximum input toggle rate to maintain diagnostic fault coverage <20/sec
12 FVD Off state glitch
Duration
Magnitude
Output Impedance <2 ms
about 36% test voltage
0–5 VDC, about 100 k:
13 ADC scan time <1 ms for all 32 points
14 Functional earth to protective earth isolation 500 VDC, minimum
15 Functional earth to functional earth (logic ground) isolation 800 VDC, minimum
16 Origin Country Made in U.S.A
17 Supplier Aotewell
Digital Input Module Each TMR Digital Input Module has three isolated sets of electronics, called channels, which independently process field data to the module. Each channel places the processed data in an array and transmits this array, on request, to the MP associated with that channel. The MPs vote on the data before passing it to the application. DI Modules include complete, ongoing diagnostics for each channel. If the diagnostics detect a failure on any channel, the Fault indicator turns on and activates the system alarm. The Fault indicator identifies a channel fault, not a complete module failure. The DI Module continuously verifies the ability of the system to detect transitions to the opposite state. DI Modules are guaranteed to operate properly in the presence of a single fault and may continue to operate properly with multiple faults. DI Modules support a hot-spare module. Each DI Module is mechanically keyed to prevent improper installation in a configured baseplate. The Model 3301 DI Module can be used with these baseplates: • Model 2301, which is used with typical applications. • DI External Termination Baseplate, which is used with the Solid State Relay Input External Termination Panel in high-voltage applications, or the Model 9573-610 DI Hazardous Location External Termination Panel.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!