Description
Highlights
The IISAC01 Analog Control Station (SAC) provides process loop control and monitoring capabilities for a single loop. The analog control station receives and sends information to and from the
Harmony controller through the CIO-100 control I/O block, the IMCIS12 control I/O module, or
the IMQRS12 quick response module. It includes features not found on earlier digital control
stations:
■ Additional analog input display with square root option.
■ High resolution bar graph displays.
■ Five or 40-kilobaud serial link.
Specifications
Property Characteristic/Value
Displays 3 gas plasma bar graphs (200 segments for process variable and set
point at 0.5% resolution, 100 segments for output at 1.0% resolution)
8-character, 14-segment, alphanumeric display
Bypass Automatic entry or selected from faceplate
Communication 5 or 40 kbaud RS-485 serial link to the controlling module through the
termination unit
40 kbaud with IMMFP11 and IMMFP12 modules with firmware revision
level E_0 or higher
Size 72 x 144 x 381 mm (2.82 x 5.67 x 15.0 in.)
Mounting Flush panel mounting
Supply voltage
(at the termination device)
21.6 VDC minimum, 27.0 VDC maximum
Power consumption
(at the termination device)
540 mA at 24 VDC
Analog output:
Current 3 to 21 mA
Load
Compliance
Inductance
600 Ω maximum
600 mH maximum
Accuracy 2.0% of span at 25°C (77°F)
D/A resolution 8 bits
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!