Description
EMERSON CE4003S2B1 12P2532X152 KJ3222X1-BA1
In addition to traditional I/O cards, the local bus supports
fieldbus technologies, including FOUNDATION Fieldbus,
Profibus DP, DeviceNet and AS-i protocols. The I/O subsystem
also supports Serial interface cards as well as the Ethernet I/O
interface. These various I/O products provide a wide range of
interfaces to meet the needs of your control application.
The SQ controller also supports CHARMs and WirelessHART
I/O cards. The CHARM I/O Card (CIOC) connects via the
redundant Ethernet ports of the controller to provide a
highly distributed and flexible I/O solution called Electronic
Marshalling. Up to 16 CIOC’s can communicate to one
controller, each providing up to 96 individually configurable
signal types.
The capacity limits of the SQ controller may vary depending
on the particular application, amount of CHARM I/O Signals and
as well control performance requirements. Enhanced memory
handling and hardware alerts covering capacity and memory,
via indexes, got added to the diagnostic information’s of the
SQ controller.
The WirelessHART I/O card (WIOC) provides redundant
communication for up to 100 WirelessHART devices,
providing high availability and reliability of wireless data.
Up to 16 WirelessHART I/O cards can communicate to
one controller, each providing up to 100 signals.
Control modules are automatically scheduled by the controller,
based on their assigned scan rates. This allows each control
function to be optimized based on the process dynamics.
Modules scan times can be set as fast as 100 ms, and as slow
as 60 seconds. The number of control modules that can be
assigned to a controller depends on the complexity and scan
rate of each module, and the available CPU and memory.
The SQ controller should be used for small to medium
applications with a maximum of 750 individual I/O signals.
The SQ controller is designed for harsh environments and
is rated for G3 corrosive environments, with an operating
temperature range from -40 to 70°C. It is ideally suited for
remote installation, close to the process equipment. For more
traditional installations with central marshalling cabinets,
CHARM I/O Cards can be mounted in standard I/O cabinets
providing Electronic Marshalling. CHARM I/O Cards can also
be used for highly distributed I/O applications.
Specifications for the SQ Controller
DST Limit 750
SCADA Tags 3200
Max Data Values Sent 2000/second
Max Data Values Received 250/second
Max Unsolicited Client Nodes 64
Module Execution Rates 100ms, 200ms, 500ms, 1s, 2s, 5s, 10s, 30s, 60s
User Memory 48 MB
Fuse Protection (Internal) 3.0 A, non-replaceable fuses
Power Dissipation 5.0 W typical, 7.0 W maximum
Environmental Specifications
Operating Temperature* -40° to 70°C (-40° to 158°F)
Storage Temperature -40° to 85°C (-40° to 185°F)
Relative Humidity 5 to 95%, non-condensing
Protection Rating IP 20
Airborne Contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Shock (Normal Operating Conditions) 10 g ½-sine wave for 11 ms
Vibration (Operative Limit) 1 mm peak-to-peak from 5 Hz to 13.2 Hz,
0.7 g from 13.2 Hz to 150 Hz
LED Indicators
Green – Power Indicates DC power is applied
Red – Error Indicates an error condition
Green – Active Indicates that the controller is operating as the
primary controller
Green – Standby Indicates that the controller is operating as a backup controller
Yellow Flashing – Pri. CN Indicates valid primary control network communication
Yellow Flashing – Sec. CN Indicates valid secondary control network communication
External Connections
Primary Control Network 8-pin RJ-45 connector
Secondary Control Network 8-pin RJ-45 connector
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!