FBM212 P0914XL Input module

FBM212 P0914XL

14 group isolated differential thermocouple/mV input channels and one reference junction
temperature compensation channel.
Input Range -10.5 to +69.5 mV dc (-10.5 to +69.5 mV dc equals 0 to 64000 raw counts. Inputs of
71.419 mV dc equals 65535 raw counts (full range of module)).
Reference Junction 3-wire 100 ohm platinum RTD (IEC 751, Class B) is internally provided at the termination
assembly. Channel 15 is the cold junction compensation channel. The RTD is in the TA
and is not customer accessible.
Accuracy • Millivolt Input:
±0.03% of span (±27 μV) at 25°C
• RTD Channel:
±0.03% of span
• RTD Reference Junction Conformity:
±0.25°C
• Thermocouple Conformity:
±0.25°C
• Accuracy Temperature Coefficient:
±50 ppm/°C
• RTD Reference Junction Measurement Accuracy(b):
±0.50°C (When using the RTD internal to the Foxboro-supplied termination blocks)
• Differential Input Impedance:
10 MΩ
• Common Mode Voltage:
±2.5 V dc or peak ac between channels

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

The Differential Thermocouple/mV Input Module (FBM212) contains 14 differentially
isolated thermocouple input channels, and one differentially isolated RTD reference
junction temperature compensation channel (for terminal temperature sensing). Each
thermocouple/mV channel accepts standard thermocouples for various temperature
ranges, and each provides thermocouple burnout detection (up-scale). Each channel
has a differential input to allow voltage differences between channels without
introducing detected errors.
The module performs the signal conversion required to interface the electrical input
signals from the field sensors to the optionally redundant Fieldbus. It executes an
analog input application program, which provides configurable options for Conversion
Time and Rate of Change Limits.
Features
• 14 channels for input of thermocouple signals
• 1 isolated RTD reference junction compensation channel (for terminal
temperature sensing)
• Each channel has a differential input
• Rugged design suitable for enclosure in Class G3 (harsh) environments
• Execution of an analog input application program that provides conversion time
and configurable options for Rate of Change Limits
• High accuracy achieved by sigma-delta data conversions for each channel
• Termination Assemblies (TAs) for locally or remotely connecting field wiring to the
FBM212

FBM212 P0914XL

FBM212 P0914XL

4a10df36f26543d4c69b FBM212 P0914XL Input module ef3b9c0b936f37a17d83 FBM212 P0914XL Input module

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!