GE 12HGA11J52
The AC voltage or DC current relays are adjusted to pick up at 70-80 percent of
rating at rated frequency. The DC voltage relays are adjusted to pick up at 50-60
percent of rating when cold.
After AC relays have been continuously energized for a few hours (minimum four hours ) at rated voltage, the pickup and dropout voltages increase by 3.5 to 7.5
percent,
percent.
For DC relays, the pickup and dropout voltages increase by 5 to 10
The wipe on HGA11 relays exerts a contact pressure of 35 grams + 10 percent on
” a” contacts and 10 grams + 10 percent on “b” contacts.
CONSTRUCTION
The HGA11 is a molded case relay. The various parts of the relay can be seen
in Figure 10. The control spring is used for adjusting the pickup and dropout
voltage. The function of the voltage barrier is to avoid flashover between a pair
of electrically separate, but mechanically coupled normally closed contacts, or
between a pair of normally open contacts. Cover spring clips maintain spring force
against the cover to hold the cover in position.
RECEIVING, HANDLING AND STORAGE
These relays, when not included as part of a control panel will be shipped in
cartons designed to protect them against damage. Immediately upon receipt of a
relay, examine it for damage sustained in transit. If damage resulting from rough
handling is evident, file a damage claim at once with the transportation company and
promptly notify the nearest General Electric Apparatus Sales Office.
Reasonable care should be exercised in unpacking the relay in order that none
of the parts are damaged nor the adjustments disturbed.
If the relays are not to be installed immediately, store them in their original
cartons in a place that is free from moisture, dust and metallic chips. Foreign
matter that collects on the outside of the case could get inside when the cover is
removed, and cause trouble when operating the relay.
PERIODIC CHECKS AND ROUTINE MAINTENANCE
In view of the vital role of relays in the operation of a power system, it is
important that a periodic test program be followed. The interval between periodic
checks will vary depending upon environment, type of relay and the user ‘ s experience
with periodic testing. Until the user has accumulated enough experience to select
the test interval best suited to his individual requirements, the points listed
under ACCEPTANCE TESTS should be checked at an interval of from one to two years.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!