Description
8115-DO-DC
• 8 powered outputs
• Controls solenoids and relays
• Common load supply of up to 60 V dc
• Discrete or pulsed outputs
• 1A per channel switched current
• 2–60 V dc bussed field power required
MODULE SPECIFICATION
See also System Specification
INPUTS
Number of channels
• 8
Output voltage range
• 2–60 V dc
ON voltage drop
• 0.25 V (max.)
OFF leakage current
• 1.0 mA (max.)
Switched current per channel††
• Continuous*
– 1 A
• For < 100 ms – 4 A
• For < 20 ms – 6 A
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Fail-safe
• Predefined value / last value
Output
• Discrete, momentary or continuous pulse‡
Pulse width
• 2 ms to 130 s
RESPONSE TIME
Response time
• From Railbus command to output change –
1 ms (max.)
POWER SUPPLIES
Railbus (12V) current
• 45 mA (typ.)
• 70 mA (max.)
Bussed Field Power
• 2 to 60 V dc
MECHANICAL
Module Key Cod
• B6
Module width
• 42 mm
Weight
• 200 g