GE IC670MDL644 IC670MDL730 IC670MDL740 modular

Wiring Examples with Auxiliary Trminal Blocks
If the module is installed on an I/O Terminal Block with Barrier Terminals, an Auxiliary Terminal
Block can be used to provide additional wiring terminals. For the I/O Terminal Block with Wire to
Board Connectors, external connection points are usually preferred, although an Auxiliary
Terminal Block can be used.
Auxiliary Terminal Blocks have all terminals connected together intermally. The Auxiliary
Terminal Block with box terminals has 13 terminals, each of which accommodates one AWG #14
(avg 2.1mm2 cross section) to AWG #22 (avg 0.36mm2 cross section) wire, or two wires up to
AWG #18 (avg.0.86mm2 cross section). The Auxiliary Terminal Block with barrier terminals has
nine terminals, each of which can acommodate one or two wires up to AWG #14 (ayg 2. lmm2
cross section).
The following ilustration shows how an Auxiliary Terminal Block with Box Terminals can be
used for power connections to an I/O Terminal Block with Box Terminals.

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

IC670MDL644
Module Characteristics
Rated Voltage
24VDC
Input Voltage Range
0-30 VDC
User Input Current
8.0 mA per point @ 24 VDC
Isolation:
User input to logic, user input to
250 V AC continuous, 1500 VAC for 1 minute.
frame ground,
Point to point
No isolation between individual points in a group
Indicators
1 LED per point shows individual point status
PWR LED indicates field and backplane power are present
Current drawn from Bus
80 mA
Interface Unit Power Supply
Input Characteristics
Input Impedance
3K Ohms typical
On state voltage
Positive logic: +15V to +30V
Negative logic: -15V to -30V
Off state voltage
Positive logic: 0 to +5V
Negative logic: 0 to -5V
On state Current
3.0mA to 8.0mA
Off state Current
0mA to 1. 5mA
On response time.
25 μs typical, 60 us maximum
Off response time
100 μs typical, 150 μs maximum

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!