HIMA F35

¥13,000.00

HIMA F35
The controller is equipped with 8 digital outputs. The state (HIGH, LOW) of each output is
signaled by an individual LED.
At the maximum ambient temperature, each of the outputs 1…3 and 5…7 can be loaded
with 0.5 A, and outputs 4 and 8 can be loaded with 1 A or 2 A at an ambient temperature of
up to 50 °C.
If an overload occurs, one or all outputs are switched off. If the overload is removed, the
outputs are switched on again automatically, see Table 28.
The external wire of an output is not monitored, however, a detected short-circuit is
signaled.

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

The safety-related F35 controller is a compact system located in a metal enclosure with 24
digital inputs, 8 digital outputs, 2 counters and 8 analog inputs.
The controller is available in 3 model variants for SILworX and 3 model variants for
ELOP II Factory, see Chapter 3.2. All variants are described in this manual.
The controller is equipped with safety-related digital inputs and outputs, safety-related
counters and safety-related analog inputs.
Safety-Related Digital Inputs
The controller is equipped with 24 digital inputs. The state (HIGH, LOW) of each input is
signaled by an individual LED.
The input signals are captured as analog measurements and provided to the program as a
range of INT values from 0…3000 (0…30 V). Configurable thresholds are used to generate
BOOL values, see Table 26
The default setting is:
Low level: < 7 V High level: > 13 V
The thresholds are set using system parameters taking the safety-related accuracy into
account, see Table 43 and Table 44.
078c7954539fd7587252 HIMA F35

a958660b4766627ca16d HIMA F35

6b37ceaae7b2e949dea6 HIMA F35
For the external wiring and the connection of sensors, apply the de-energized-to-trip
principle. Thus, if a fault occurs, the input signals adopt a de-energized, safe state (low
level).
An external wire is not monitored, however, an open-circuit is considered as safe low level.
3.1.1.1 Reaction in the Event of a Fault
If the device detects a fault on a digital input, the user program processes a low level in
accordance with the de-energized to trip principle.
The device activates the FAULT LED.
In addition to the channel signal value, the user program must also consider the
corresponding error code.
The error code allows the user to configure additional fault reactions in the user program.

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!