Description
HONEYWELL 8C-PCNT01
C300 Configuration Options
50 ms CEE 20 ms CEE4
Control Networks Supported FTE only 1 FTE only 1
Supported C300 Models 6, 7 CC-PCNT01
CC-PCNT02
CC-PCNT01
CC-PCNT02
Device Index Configuration Between 1 and 510 Between 1 and 510
IOTA Size 6 inches 6 inches
Number of I/O Links Supported 2 2
I/O Link Speeds Available 375 Kbaud (PMIO Link)
750 Kbaud (Series C IO
Link)
750 Kbaud (Series C IO
Link)
375 Kbaud (PMIO Link) is not
supported
Base Execution Periods Supported 50 ms 20 ms (optional)4
Redundancy Supported Yes Yes
Remote – Non-Series C I/O Supported Yes – PM I/O or Series A
I/O 3
No – Only Series C I/O
supported with limited
capacities.
I/O Module Execution Period 50 ms 20 ms
Configurable Values for CM/SCM/RCM Execution Periods 5 50, 100, 200, 500, 1000,
2000, 5000, 10000,
20000, 300000, 60000
ms.
20, 40, 80, 200, 400, 800
ms.
CMs Only – SCM/RCM/MR
not supported
Configurable Values of Peer Update Rates (period).
Defines the period at which data is updated for all ‘pull/get’
requests for peer data required by all blocks within a CEE.
100, 200, 500, 1000 ms. 100, 200, 500, 1000 ms.
C300 Time Source SNTP, PTPv2 SNTP, PTPv2
SNTP Update Period 1 minute 1 minute
GPS Time Support2 No No
PTP Update Period 30 seconds 30 seconds
C300 Redundancy Specifications
50 ms CEE 20 ms CEE4
C300 Function Block Redundancy Configuration Selection: “Module is Redundant” “Module is Redundant”
Number of IOTAs used for Redundant C300 2 2
Redundant Device Index Configuration Device Index = n, where
n is an odd value
Partner Device Index = n+1
Device Index = n, where
n is an odd value
Partner Device Index = n+1
Redundancy Cable Medium Ethernet STP Ethernet STP
Redundancy Cable Lengths 36, 48, 60, 84 inches 36, 48, 60, 84 inches
Control Processing Switchover Interruption Time1,2 500 ms 200 ms
Initial Synchronization Time (from Sync Start to
Completion)
240 seconds 240 seconds
Maximum Elapsed Time Between Commanded Switchover
and Completion of Initial Synchronization
500 seconds 500 seconds
Maximum Elapsed Time Between Switchover Due to Power
Cycle of the Primary and Completion of Initial
Synchronization
500 seconds 500 seconds
Maximum OPM Control Freeze time 20 seconds 20 seconds
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!