Description
HONEYWELL CC-TAON01
I/O Module Functions
• High Level Analog Input /HART Input Module (16pt) – The High Level Analog Input Module supports both high
level analog and HART inputs. Analog inputs are typically 4-20mA DC for both traditional and HART devices. HART
data can be used for status and configuration. HART data, such as the secondary and tertiary variables, can also be
used as process control variables. Two versions are available.
• High Level Analog Input w/o HART (16pt) – The High Level Analog Input Module supports high level analog inputs
Analog inputs are typically 4-20mA DC for traditional devices.
• Analog Output/HART Output Module (16pt) – The Analog Output Module supports both standard 4-20mA DC
outputs and HART transmitter outputs. Two versions are available.
• Analog Output w/o HART (16pt) – The Analog Output Module supports standard 4-20mA DC outputs.
• Digital Input 24 VDC (32pt) – Digital input sensing for 24V signals. Two versions are available.
• Digital Input High Voltage (32pt) – Digital input sensing for 110 VAC, 220 VAC, 125VDC.
• Digital Output 24 VDC (32 pt) – Current sourcing digital outputs. Outputs are electronically short-circuit protected.
Two versions are available.
• Relay Digital Output (32 pt) – Digital output with NO or NC dry contacts. Can be used for low power or high power
applications.
• Temperature Multiplexer (64 pt) – Provides thermocouple (TC) and resistance temperature device (RTD) inputs.
The Multiplexer supports up to four, field proven PMIO FTAs.
• Temperature Multiplexer (64 pt) – Provides thermocouple (TC) and resistance temperature device (RTD) inputs.
The Multiplexer supports up to four, field proven PMIO FTAs
• Pulse Input (8pt) – Provide linear counting, PV generation, and Quaduature Input for Custody Transfer
• Universal Input Output (32 pt) – Supports 32 channels of user configurable IO. Choices available – analog input,
analog output, digital input, and digital output
Function
The Analog Input Module accepts high level current inputs from transmitters and sensing devices.
Notable Features
• Extensive self-diagnostics
• Optional redundancy
• Supplies non-incendive field power (No external
user supplied power)
• Suitable for Configure / Status for HART devices
• HART-capable, multivariable instruments for fast
collection of control variables
• Fast loop scan
• Non-Incendive Power
Detail Specifications – Analog Input with HART
Parameter Specification
Input / Output Model CC-PAIH51 – High-Level Analog Input with HART
IOTA Models CC-TAIX51 Non Redundant 6”
CC-TAIX61 Redundant 12”
Input Type Current (2-wire or self-powered transmitters)
Input Channels 1 16 Channels (ALL Single Ended).
Common Mode Rejection Ratio, dc to 60 Hz (500
source imbalance)
70 dB
Common Mode Voltage, dc to 60 Hz -6 to +5 V peak
A/D Converter Resolution 16 bits
Input Range 1 4-20 mA only (through 200 Ω)
Normal Mode Rejection Ratio, at 60 Hz 19 dB
Normal Mode Filter Response Single-pole RC, -3 dB @ 6.5 Hz
Maximum Normal Mode Input ± 30 Volts
Crosstalk, dc to 60 Hz (channel-to-channel) -60 dB
Input Scan Rate 50 ms
Hardware Accuracy (@ CMV = 0 V) ± 0.075% of full-scale (23.5°± 2°C)
± 0.15% of full-scale (0 to 60°C)
Transmitter Field Power Conditioning Individually Protected Current Limiting Circuits for Class 1,
Div 2 non-incendive interfacing. No fusing required
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!