Cable Assembly Replacement
It is not intended that the cable should need replacement, however this may be achieved by
replacement of the complete cable assembly that requires that the system be shutdown. To remove a
cable:
Ensure that the correct chassis and slot positions are selected.
Ensure the associated chassis slots are not occupied by modules.
Press in the hood release button and slide the hood downwards.
Remove the hood from the chassis slot by sliding down and rearward.
To insert a new or replacement cable:
Ensure that the correct chassis and slot positions are selected.
Ensure that the associated chassis slots are not occupied by modules.
Present the connector to the chassis backplate slot, taking care to align the lugs of the
connector with the cut-outs of the slot.
Push the connector hood in and upwards into the slot until the latch engages with the
backplate lip.
Ensure that the connector hood is secure in its position.
Where it is critical to maintain system operation additional chassis may be installed and on-line
operation maintained by transferred control to modules within that chassis using the I/O modules
SmartSlot capability.

Category:
Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!

Description

ICS TRIPLEX T8310
Module Replacement
The replacement module must be inserted in to the vacant processor slot, ensuring that the module is
correctly located and the ejector tabs are closed (see 2.2). The newly installed module will perform its
power-up sequence.
Ensure that the LED indicators on the newly installed module are as follows:
LED 1 Healthy A Steady Green
LED 2 Healthy B Steady Green
LED 3 Healthy C Steady Green
If the original module has reported faults, the TMR Processor may automatically initiate the
changeover to the newly installed module. Manual changeover may be initiated either using the ejector
tabs on the original module or using commands via the diagnostic interface. To initiate the changeover
using the ejector tabs use the following sequence:
1. Release both the top and bottom ejector tabs on the original module using the ejector release
tool. DO NOT remove the module.
2. Wait until the original module indicates that it is in the standby mode of operation and the
newly installed module is in the active mode.
3. Remove the original module.
Note: Under no circumstances remove a module that is indicating ACTIVE mode. Removal of an
active module may result in modules within the chassis adopting their default (shutdown) state,
and initiate shutdown states via the application program.
In Hot-standby configurations, with both Expander Interface Modules installed, the faulted module may
be either the active or the standby module. In most cases the system will automatically switch to the
healthiest module, therefore only the standby module will require replacement. To replace the active
module follow the steps described above. To replace the standby module:
1. Release both the top and bottom ejectors tabs on the standby module using the ejector
release tool.
2. Ensure that the other module is indicating the active mode of operation.
3. Remove the standby module.
In Hot-standby configurations, the replacement module should then be installed in the position where
the previous module was removed. This module will become the standby module.
ce94fc85efaa8ac65773 3 scaled ICS TRIPLEX T8310

a7441d550327dfa0a61f 3 scaled ICS TRIPLEX T8310

3f21b4b36fed81d37e21 3 scaled ICS TRIPLEX T8310
3f21b4b36fed81d37e21 3 scaled ICS TRIPLEX T8310

a7441d550327dfa0a61f 3 scaled ICS TRIPLEX T8310

ce94fc85efaa8ac65773 3 scaled ICS TRIPLEX T8310

Email: Jiedong@sxrszdh.com
Phone: +86 15340683922
Sales:Wu Jiedong
Our products are guaranteed for 1 year, with new and original production stopped and imported spare parts.
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!