Description
DO3401
Feature Feature Specification
Points 16, commoned
Nominal output voltage 24 VDC
Specified operational voltage range 15 to 30 VDC
Absolute maximum output voltage 33 VDC
Absolute maximum reverse input voltage – 0.6 VDC
Output current
Switching
Degraded mode
<4.8 A, self-limiting 3.0 A, typical
> 0.7 A, self-limiting 1.5 A, typical
Field alarms Loss of field power, output point shorted On or Off
Loop-back thresholds 0–5 VDC = Off region 6–14
VDC = transition region
15–30 VDC = On region
Leakage to load (Off state) <1 mA
Diagnostic glitch duration <2 ms, maximum 500 Ps, typical
Diagnostic fault coverage
Maximum toggle rate
Minimum toggle rate
20 ms
Not applicable
On state voltage drop <1.0 VDC @ 1.5 A
Loop-back scan time <1.0 ms for all 16 points
Functional earth to protective earth isolation 500 VDC, minimum
Functional earth to functional earth (logic) isolation 800 VDC, minimum
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!