Description
3481 TRICONEX Model 3481 Analog Output Module Specifications 3481
Feature Specification
Points 4, commoned-return, DC-coupled
Isolated points None
Output current range 4–20 mA output, controlled
0–22 mA over-range
0 mA output capability (step function < 2 mA)
Output accuracy <0.25% (in range of 4–20 mA) of FSR (0–22
mA), from 32° F to 158° F (0° C to 70° C)
Type TMR
Resolution 12 bits
Diagnostic Forced-switch diagnostic (FSD)
External loop power (reverse
voltage-protected)
32 VDC, maximum
24 VDC, nominal
Output loop power requirements
for specified load
300 ??@ >16 VDC (1 A minimum)
500 ??@ >20 VDC (1 A minimum)
700 ??@ >24 VDC (1 A minimum)
800 ??@ >28 VDC (1 A minimum)
Over-range protection 36 VDC, continuous
0 VDC, continuous
Switch time on leg failure 1 ms, typical
3 ms, maximum
All prices listed on the official website are subject to confirmation by contact: Wu Jiedong (manager).
Our product: brand new original packaging
Our warranty: All new or repaired parts have a 12 month warranty period beginning
Our payment: 100% telegraphic transfer of inventory items before shipment, conditions can be proposed!
If you have any downtime spare parts that you cannot find, please feel free to call or use email to contact me. If there are issues that the product cannot solve, please contact me. Product prices can be negotiated. Please do not consider contacting me!